12.9. VERIFY OF PROTECTION COORDINATION L-L, L-N AND L-PE
Purpose of the test

Test the coordination of protective devices (typically MCB or fuse) present in a Single-
phase or Three-phase installation as a function of the limit time of fault extinction by the
protection set by the user and the calculated value of the short-circuit current.


Parts of the system to be checked
The test must be performed at the point in which the minimum short-circuit current is
possible, normally at the end of the line controlled by the protection device in the normal
condition of the line. The test must performed between Phase-Phase in the Three-phase
installations and between Phase-PE or Phase-PE in the Single-phase installation

Allowable values
The instrument performs the comparison between the calculated value of short-circuit
current and the Ia = tripping current of the protection device within the specified time,
accordinf to to following expressions:

a

Min

L

L

SC

I

I

2

_

Three-phase system  Loop L-L impedance

a

Min

N

L

SC

I

I

 _

Single-phase system  Loop L-N impedance

a

Min

PE

L

SC

I

I

_

Single-phase system  Loop L-PE impedance

where:

Isc L-L_Min2F

= Prospective short-circuit current minimum double phase L-L

Isc L-N_Min

= Prospective short-circuit current minimum L-N

Isc L-PE_Min

= Prospective short-circuit current minimum L-PE

The calculation of prospective short-circuit current is performed by the instrument based
on the fault loop impedance measurement in compliance with the following relationships
derived from standard EN60909-0:

L

L

NOM

L

L

MIN

Min

L

L

SC

Z

U

C

I

2

_

N

L

NOM

N

L

MIN

Min

N

L

SC

Z

U

C

I

_

PE

L

NOM

PE

L

MIN

Min

PE

SC

Z

U

C

I

_

L

Phase – Phase

Phase – Neutral

Phase – PE

Measured voltage

U

NOM

C

MIN

230V-10% < Vmeasured < 230V+ 10%

230V

0,95

230V+10% < Vmeasured < 400V- 10%

Vmeasured

1,00

400V-10% < Vmeasured < 400V+ 10%

400V

0,95


where:

U L-L

= Nominal Phase-Phase voltage

U L-N

= Nominal Phase-Neutral voltage

U L-PE = Nominal Phase-PE voltage
Z L-L

= Impedance Phase-Phase measured

Z L-N

= Impedance Phase-Neutral measured

Z L-PE = Impedance Phase-PE measured