HT instruments MACROTEST G3 User Manual

Page 73

Advertising
background image

MACROTESTG3 - COMBIG3

EN - 72

1. Select the option “50Hz or 60Hz” and the reference

Phase-Neutral or Phase-Phase voltage in the general

settings of the instrument (see § 5.1.3). Touch the

icon and then the

icon. The screen to the side

appears on the display. Touch the lower left icon to set
the type of measurement. The following screen appears
on the display

2. Move the second slide bar reference and select the

type of measurement between the options: L-L (Phase-
Phase measurement) or L-N (Phase-Neutral
measurement).

Move the third slide bar reference and select the

icon to carry out measurement with the optional
accessory IMP57 (see § 6.4.9). Move the first slide bar
reference thus selecting options:

 Impedance measurement performed with the

instrument only. With this option the icon “

” is

shown on the display

 Possibility for the operator to manually

set the Offset Z1 impedance without carrying out
the first measurement. With this option the icon

” is shown on the display and the following

screen appears on the display

3.

Touch the icon

to zero the value in the “

” field and

use the virtual keyboard to set the value of the Offset
Z1
impedance within the range 0.000

 to 9999.

Confirm the selection and go back to the previous
screen. Touch the second lower icon and set the value
of the rated current of the protection device on the main
line being tested. The following screen appears on the
display

4. Touch the icon to zero the value in “A” field and use

the virtual keyboard to set the value of rated current of
protection device in the range 1A to 9999A. Confirm
selection and go back to the previous screen.

Touch the third lower icon and set the maximum
allowed limit value of voltage drop (

V%) for the main

line being tested. The following screen appears on the
display.