MACROTESTG3 - COMBIG3

EN - 61

1. Select the options “TN, TT or “IT”, “25 or 50V”, “50Hz or

60Hz” and the reference voltage in the general settings

of the instrument (see § 5.1.3). Touch the

icon. The

screen to the side (TT and IT systems) is shown on the
display. The instrument automatically carries out the
test in presence of voltage between the inputs (shown
on the display) and blocks the test in case of voltage
higher than 10V
Touch the first icon in the lower left corner to set the
measuring mode. The following screen appears on the
display:

2. Move the slide bar reference in the position "

" for

the selection of the earth measurement with
voltammetric method, in the

position for the

resistance measurement with use of optional clamp
T2100 (see § 6.7.2) or in the "

" position for the

measurement of ground resistivity. Confirm the choice
by going back to the initial measurement screen.

Touch the second icon in the lower left corner to set the
tripping current of the differential switch (TT and IT
systems
). The following screen appears on the display:

3. Move the slide bar reference in the position

corresponding to the value of the tripping current of the
RCD differential switch as shown in the screen to the
side. On the basis of this selection and the value of
contact voltage (25V or 50V), the instrument performs
the calculation of the limit value of earth resistance (see
§ 12.11) that will compare with the measured value in
order to provide the final positive or negative result of
the measurement.

4. For TN systems, the instrument shows the initial

screen as in the figure to the side.

Touch the central icon to set the rated current of the
RCD. The following screen appears on the display: