HT instruments MACROTEST G3 User Manual

Page 41

Advertising
background image

MACROTESTG3 - COMBIG3

EN - 40

4.

Touch the

icon to zero the value in the In field and

use the virtual keyboard to set the value of the RCD
rated current within the values allowed by the
instrument.

The following selections are available on the instrument

MCB current (B curve) selectable among:

6,10,13,15,16,20,25,32,40,50,63A

MCB current (C, K curves) selectable among:

0.5,1,1.6,2,4,6,10,13,15,16,20,25,32,40,50,63A

MCB current (D curve) selectable among:

0.5,1,1.6,2,4,6,10,13,15,16,20,25,32A

Nominal current Fuse gG selectable among:

2, 4, 6, 8, 10, 12, 13, 16, 20, 25, 32, 40, 50, 63, 80,
100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
1000, 1250A

Nominal current Fuse aM selectable among: 2, 4, 6,

8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125,
160, 200, 250, 315, 400, 500, 630A


Confirm the choice by going back to the previous
screen.

Touch the icon in the bottom right corner to set the
type, section and material forming the inner insulation
of the cable of the line under test. The following screen
appears on the display:

5. Touch the “mm

2

” field and, by using the virtual

keyboard, set and confirm the section value of the
single cable free selectable

Touch the field “

”and, by using the virtual keyboard,

set and confirm the possible number of parallel cords.
In the case that the circuit have only one conductor set
the “1” value

Move the central slide bar reference by selecting the
type of conductor. The available options are Cu
(Copper) and Al (Aluminum).

Move the right slide bar reference by selecting the
insulation type of the cable between the options: PVC,
Rub/Butil (Rubber/Butyl rubber) and EPR/XLPE
(Ethylene propylene rubber/Cross-linked polyethylene)

Confirm the choice by going back to the initial
measurement screen.