10 Press the GO/STOP key on the instrument to measure

the Z2 impedance and complete the

V% voltage drop

measurement. During this whole stage, do not
disconnect the measuring leads of the instrument from
the system being tested

In case of positive result (maximum percentage value
of calculated voltage drop according to § 12.11 <
set limit value)
, the screen to the side is displayed by
the instrument, which contains the value of the Z2 end
of line impedance together the Z1 (Offset) value.

Press the SAVE button or touch the

icon to save

the measurement (see § 7.1)

11 In case of negative result (maximum percentage

value of calculated voltage drop according to §
12.11 > set limit value
), the screen to the side is
displayed by the instrument, which contains the value
of the Z2 end of line impedance together with the Z1
(Offset)
value. Press the SAVE button or touch the

icon to save measurement (see § 7.1)