EN - 25

6.3.2. x½, x1, x2, x5 modes
9. Press the GO/STOP key on the instrument or the

START key on the remote lead. The instrument will
start the measurement.

The screen to the side (concerning multiplier x1) is
shown on the display when the hourglass icon indicates
the performance of the test.

10 At the end of the test with multiplier x1/2, x1, x2 or x5 if

the tripping time, for molded case type STD, is as
listed in Table 4

the instrument shows the

symbol to signal that the

test has been completed successfully, and displays a
screen similar to the one reported here to the side.

Press the SAVE button or touch the

icon to save

the measurement (see § 7.1).

11 At the end of the test, for molded case type STD, if the

tripping time of a test does not comply with what is

indicated in Table 4the instrument shows the

symbol to signal that the test has not been completed
successfully, and displays a screen similar to the one
reported here to the side.

Press the SAVE button or touch the

icon to save

the measurement (see § 7.1).

6.3.3. Mode x1 – Test on RCDs with delay time
9. At the end of the test, if the measured tripping time is

within the interval: [limit delay = set delay time +
value indicated in Table 4]
the instrument displays

the

symbol to indicate the positive outcome of the

test and displays a screen like the one to the side.

Press the SAVE button or touch the

icon to save

the measurement (see § 7.1).

10 At the end of the test, if the measured tripping time is

external the interval: [limit delay = set delay time +
value indicated in Table 4]
the instrument displays

the

symbol to indicate the negative outcome of the

test and displays a screen like the one to the side.

Press the SAVE button or touch the

icon to save

the measurement (see § 7.1)