MACROTESTG3 - COMBIG3

EN - 59

6.7.

EARTH:

MEASUREMENT OF EARTH RESISTANCE

The MACROTESTG3, MOD1, MOD2 models (or COMBIG3 with EARTH function enabled)
allows performing the measurement of earth resistance of an installation in the following
ways:

Measurement of earth resistance with 3-wire or 2-wire voltammetric method

Measurement of ground resistivity (

) with Wenner 4-wire method

Measurement of resistance of individual rods without disconnecting them by means of

the optional clamp T2100


6.7.1. 3-wire or 2-wire earth measurement and 4-wire ground resistivity
The measurement is carried out in compliance with standards IEC/EN61557-5.

CAUTION

 The instrument can be used for measurements on installations with

overvoltage category CAT III 240V to earth with a maximum voltage of
415V between inputs. Do not connect the instrument to installations with
voltages exceeding the limits indicated in this manual. Exceeding these
limits could result in electrical shocks to the user and damage to the
instrument.

 Always connect the measuring cables to the instrument and to the alligator

clips with the accessories disconnected from the system.

 We recommend holding the alligator clip respecting the safety area created

by the hand protection (see § 4.2).

 If the length of the cables supplied is not suitable for the installation under

test, you can create your own extensions following the indications in §
12.12.1.


Fig. 26: Three-wire earth resistance measurement