MACROTESTG3 - COMBIG3

EN - 66

1. Select the options “TN, TT or “IT”, “25 or 50V”, “50Hz or

60Hz” and the reference voltage in the general settings

of the instrument (see § 5.1.3). Touch the

icon,

touch the first icon in the lower left corner and set the

measurement mode

(see § 6.7.1 point 2). The

following screen appears on the display. The

icon

indicates that the clamp T2100 is not connected to the
instrument or is not in "RS232" mode. Configure the
same settings on the protection parameters depending
on the type of system (TT, TN or IT) (see § 6.7.1 points
3, 4, 5, 6).

2. Connect the clamp T2100 by inserting the connector into input In1 of the instrument.

Turn the clamp on and put it in "RS232" mode (see the user manual of the clamp). The

symbol appears on the display of the clamp. In these conditions, the instrument-

clamp group is ready to perform the measurements. The following screen is shown
on the display by the instrument.

3. The meaning of the symbols is the following:

 This icon indicate the correct serial

connection of the clamp to the instrument

 Touch this icon to zero all the values of the

measured probes and the correspondent parallel
resistance

 Touch this icon to add a rod to the

measurement. The "N " parameter increases by one
unit.

R

A

 indicates the calculation of the parallel of

resistances for each measurement performed on
each rod.

 This indicates the value of contact voltage

resulting from the measurement.

N  indicates the number of rods in the measure.

R  indicates the resistance value of the rod

currently measured.

It allows downloading on the instrument the

memory contents of clamp T2100 in order to obtain
the final result of the measurement.

Rods resistance measurement with clamp T2100 connected to the instrument

4. Connect the clamp to the first rod of the earth network considered as shown in Fig. 30.

Note the value of the resistance in the R field and press the

icon to insert this

value in the calculation of parallel resistance and increase the N parameter by one unit
(N =1)