Technical specifications – HT instruments MACROTEST G3 User Manual

Page 83

Advertising
background image

MACROTESTG3 - COMBIG3

EN - 82

10. TECHNICAL

SPECIFICATIONS

Accuracy is calculated as: ±[%reading + (no. of digits) * resolution] at 23°C, <80%RH.
Refer to the Table 1 for the correspondence between models and availbale features

10.1. TECHNICAL

CHARACTERISTICS

AC TRMS voltage

Range [V]

Resolution [V]

Accuracy

15

460

1

(3%rdg + 2digits)

Frequency

Range [Hz]

Resolution [Hz]

Accuracy

47.0

63.6

0.1

(0.1%reading+1digit)

Continuity of protective conductor (LOW

)

Range [

] Resolution

[

]

Accuracy (*)

0.01

9.99

0.01

(5.0

reading + 3digits)

10.0

99.9

0.1

(*) after calibration of measuring cables
Test current:

>200mA DC up to 2

 (cables included)

Test current resolution:

1mA

Open-circuit voltage:

4 < V0 < 24V

Insulation resistance (M

)

Test voltage [V]

Range [

] Resolution

[

]

Accuracy

50

0.01

9.99

0.01

(2.0

reading + 2digits)

10.0

49.9

0.1

50.0

99.9

(5.0

reading + 2digits)

100

0.01

9.99

0.01

(2.0

reading + 2digits)

10.0

99.9

0.1

100.0

199.9

(5.0

reading + 2digits)

250

0.01

9.99

0.01

(2.0

reading + 2digits)

10.0

99.9

0.1

100

499

1

(5.0

reading + 2digits)

500

0.01

9.99

0.01

(2.0

reading + 2digits)

10.0

199.9

0.1

200

499

1

500

999

(5.0

reading + 2digits)

1000

0.01

9.99

0.01

(2.0

reading + 2digits)

10.0

199.9

0.1

200

999

1

1000

1999

(5.0

reading + 2digits)

Open-circuit voltage

rated test voltage -0% +10%

Rated measuring current:

>1mA with 1k

 x Vnom (50V, 100V, 250V, 1000V), >2.2mA with 230k @ 500V

Short-circuit current

<6.0mA for each test voltage

Safety protection:

error message for input voltage > 10V

Line/Loop impedance (Phase-Phase, Phase-Neutral, Phase-Earth)

Range [

] Resolution

[

]

Accuracy (*)

0.01

9.99

0.01

(5%rdg + 3digits)

10.0

199.9

0.1

(*) 0.1 m

 in range 0.1  199.9 m (by using the optional accessory IMP57)

Maximum test current:

5.81A (at 265V); 10.10A (at 457V)

Phase-Neutral/Phase-Phase Test voltage: (100V

265V) / (100V460V); 50/60Hz ±5%

Protection types:

MCB (B, C, D, K), Fuse (gG, aM)

Insulating sheath materials: PVC, Butyl rubber, EPR, XLPE