HT instruments MACROTEST G3 User Manual

Page 55

Advertising
background image

MACROTESTG3 - COMBIG3

EN - 54

3. Insert the blue and black connectors of the single cables in the corresponding input

terminals of the instrument B4, B1 (2T measurement). Insert in the free end of the cables
the corresponding alligator clips or tips. It is also possible to use the remote lead by
inserting its multipolar connector into the input lead B1. Connect the alligator clips, the
tips or the remote lead to phase L1 and N according to Fig. 22 and Fig. 23.

4. Press the GO/STOP key on the instrument or the

START key on the remote lead. The instrument will
start the measurement. During this whole stage, do not
disconnect the measuring leads of the instrument from
the system under test.

The symbol for the tip on phase L1 and the hourglass
indicating the status of pending recognition of a voltage
higher than the maximum allowed.

5. Once the correct voltage recognized, the symbol is

shown on the display. The instrument gives out a long
sound until input voltage is present.

6. At the end of phase L1 acquisition, the instrument is in

standby waiting for the signal on phase L2 and showing
the symbol of "disconnected tip" as shown in the screen
to the side.

Under these conditions, connect the alligator clips, the
tips or the remote lead to phase L2 and N in
accordance with Fig. 22 and Fig. 23.

7. The symbol for the tip on phase L2 and the hourglass

indicating the status of pending recognition of a voltage
higher than the maximum allowed.

Once the correct voltage recognized, the

symbol is

shown on the display.