Iu r – HT instruments MACROTEST G3 User Manual

Page 103

Advertising
background image

MACROTESTG3 - COMBIG3

EN - 102

Check that the measured value of earth resistance is lower than the maximum limit
calculated on the basis of the maximum allowable contact voltage Utp for the system.

In accordance with the requirements of standard EN50522 the maximum allowable contact
voltage is dependent on the time duration of the fault according to the following Table 6

Fault duration [s]

Allowed contact voltage Utp [V]

10 85

5.00 86
2.00 96
1.00 117
0.50 220
0.20 537
0.10 654
0.05 716

Table 6 Maximum allowable values for contact voltage


Allowable values
The maximum earth resistance is calculated using the following relation:

g

tp

t

I

U

R

where:

Utp

= maximum allowable contact voltage in the system on the basis of the value

of Utp (the values not included in Table 6 are obtained by linear
interpolation) according to the duration time of the fault (value provided by
the Energy distribution board)

Ig

= maximum fault current in the system (value provided by the Energy

distribution board)


On the instrument, it is possible to select the value of the time duration of the fault in the
range between 0.04s and 10s and the value of the fault current in the range between 1A
and 9999A.













12.12.1.

Measurement of earth impedance by voltammetric method