MACROTESTG3 - COMBIG3

EN - 35

This mode performs the impedance measurement and the calculation of prospective short
circuit current without applying any evaluation. Therefore, at the end of the test, no outcome
is given by the instrument.


1. Select the options “TN, TT or “IT”, “25 or 50V”, “50Hz or

60Hz” and the reference voltage in the general settings
of the instrument (see § 5.1.3).

Touch the

icon. The screen to the side appears on

the display.

Touch the lower icon. The following screen appears on
the display:

2. Move the left slide bar reference by selecting the icon

to execute the measurement only with the instrument or
the

icon to execute the measurement with the

instrument + optional accessory IMP57 (see § 6.4.9).

Move the central slide bar reference by selecting the "
L-L
, L-N or L-PE” options. Move the right slide bar
reference by selecting the "STD" option. Confirm the
choice by going back to the previous screen.

3. If possible, disconnect all loads connected downstream of the measuring point, as the

impedance of these users could distort the test results.

4. Connect the shuko plug, the alligator clips or the remote lead to the electrical mains

according to Fig. 16, Fig. 17, Fig. 18 and Fig. 20.

5. Note the presence of the correct voltage values

between L-N and L-PE corresponding to the selections
carried out in the initial phase (see § 5.1.3) as shown in
the screen to the side.

Press the GO/STOP key or the START key on the
remote lead. During this whole stage, do not disconnect
the measuring leads of the instrument from the system
under test. The following screen appears on the
instrument's display: