HT instruments MACROTEST G3 User Manual

Page 31

Advertising
background image

MACROTESTG3 - COMBIG3

EN - 30

11 If the instrument detects a voltage Vn-pe > 50V (or the

analogue Vn-pe >25V) it provides the warning screen
shown to the side and blocks the test for safety
reasons. Check the PE conductor and earth plant
efficiency

12 If the instrument detects in the input terminals a too

high external impedance such that it can not provides
the nominal current, it provides the warning screen
shown to the side and blocks the test. Disconnect the
possible loads downstream the LCD before perform the
test

13 For only RCD type B if the instrument is not able to

provide for the charging of the internal capacitors of the
RCD, it provides the warning screen shown to the side
and blocks the test. Check that the VL-N voltage should
be more than 190V

14 For only RCD type B if the instrument detects a input

voltage VL-N <190V, it provides the warning screen
shown to the side and blocks the test. Chech the values
of the voltages on the installation




15 For test on earth leakage relay RCD if the value set

for the rated current of the protection device is out of
the allowed range, the instrument provides the warning
screen shown to the side and stops the tests. Change
the value of the rated current of the protection device




Advertising