Items to be calculated apparent power s [va, Reactive power q [var, Ps sign – KYORITSU 6315 Instruction Manual User Manual

Page 139

Advertising
background image

Items to be calculated

KEW6315

- 137 -

KEW6315

Items to be calculated
Apparent power S [VA]

Range

Same as active power.

Displayed digit

Same as active power.

Accuracy

±1dgt against each calculated value (for sum : ±3dgt)

Sign

No polarity indication

Equation

S

c

V

c

×A

c;

when P

c

>S

c,

regarding P

c

S

c

. c: Measurement channel

1P2W-1 to 4

S

1,

S

2,

S

3,

S

4,

S

sum

S

1

+S

2

+S

3

+S

4

1P3W-1 to 2

S

1,

S

2,

S

sum1

S

1

+S

2

S

3,

S

4,

S

sum2

S

3

+S

4

S

sum

S

sum1

+S

sum2

3P3W-2

S

1,

S

2,

S

sum1

=√

3/2( S

1

+S

2

)

S

3,

S

4,

S

sum2

=√

3/2( S

3

+S

4

)

S

sum

S

sum1

+S

sum2

3P3W3A

S

1,

S

2,

S

3,

S

sum

S

1

+S

2

+S

3 * Phase angles are used.

3P4W

S

1,

S

2,

S

3,

S

sum

S

1

+S

2

+S

3

Reactive power Q [Var]

Range

Same as active power.

Displayed digit

Same as active power.

Accuracy

±1dgt against each calculated value (for sum : ±3dgt)

Sign

: leading phase (current phase against voltage)

+ (no sign)

: lagging phase (current phase against voltage)

Harmonics reactive power is calculated per ch, and the polarity sign of the
reversed basic waveform is displayed.

Equation

Q

c

2

2

c

c

P

S

sign

sign: Polarity sign , c: Measurement channel

1P2W-1 to 4

Q

1,

Q

2,

Q

3,

Q

4,

Q

sum

Q

1

+Q

2

+Q

3

+Q

4

1P3W(3P3W)-1
to 2

Q

1,

Q

2,

Q

sum1

Q

1

+Q

2

Q

3,

Q

4,

Q

sum2

Q

3

+Q

4

Q

sum

Q

sum1

+Q

sum2

3P3W3A(3P4W)

Q

1,

Q

2,

Q

3,

Q

sum

Q

1

+Q

2

+Q

3


Advertising