Current unbalance ratio aunb, Capacitance calculation, Iumb – KYORITSU 6315 Instruction Manual User Manual

Page 141: Var 1 1 1 1, Kpf pf p c, Fpf pf v f p

Advertising
background image

Items to be calculated

KEW6315

- 139 -

KEW6315

Current unbalance ratio Aunb [%]

Displayed digit

5-digit

Display range

0.00% to100.00%

Wiring

3P3W, 3P4W

Equation

(

)

(

)

100

6

3

1

6

3

1

×



+

=

β

β

Iumb

(

)

2

2

31

2

23

2

12

4

31

4

23

4

12

A

A

A

A

A

A

+

+

+

+

=

β

* The 1st order components of harmonic current are used.

* For 3P4W system, phase voltages are converted to line voltages for

calculation.

A

12

= A

1

- A

2,

A

23

= A

2

- A

3,

A

31

= A

3

- A

1

Capacitance calculation

Displayed digit

4-digit, Unit: nF, µF, mF, kvar

Display range

0.000nF - 9999F, 0.000kvar - 9999kvar

Equation

[

]

var

1

1

1

1

2

arg

_

2

k

PF

PF

P

C

et

T

C

C

C

C



×

=

[ ]

F

PF

PF

V

f

P

et

T

C

C

C

C

µ

Ч

Ч

Ч

=

1

1

1

1

2

10

2

arg

_

2

2

9

π

C

c

: Capacitance needs for improvement

P

c

: Load power (active power)〔kW〕

f

: Frequency

V

c

: R.m.s. voltage

PF

c

: Measured PF

PF

c_Target

: New power factor (target)

c

: Measurement channel

1P2W-1 to 4

C

1

, C

2

, C

3

, C

4

, C

sum

=C

1

+C

2

+C

3

+C

4

1P3W(3P3W)-1
to 2

C

1

, C

2

, C

sum1

=C

1

+C

2

C

1

, C

2

, C

sum2

=C

3

+C

4

C

sum

=C

sum1

+ C

sum2

3P3W3A(3P4W)

C

1

, C

2

, C

3

, C

sum

=C

1

+C

2

+C

3


Advertising