Section 3 - Electrical Connections and Setup

Section 3 - Electrical Connections and Setup

Page 15

3.12

4-20 mA Isolated Outputs

Channel 1 and Channel 2

(LCD MENU SECTIONS - pH: 4.21 & 4.22, ORP: 5.20 & 5.21,

Conductivity: 6.21 & 6.22, Flow: 7.18 & 7.19)

The Shark Controller has two 4 to
20mA outputs, electrically isolated
from each other and ground. Either
output can source current into a
maximum of 800 ohms.

Channel 1 (the primary output) is
located on the flip out door, terminal
plug P6. Channel 1 is dedicated to
track the process and has fully inde-
pendent and fully adjustable 4 & 20
mA output setpoints. This will enable
the operator to span the output over
the desired range.

Channel 2 (the secondary output) is
located in the enclosure terminal
plug P1. Channel 2 can be selected
to track the process value or tem-
perature and has fully independent
and adjustable 4 & 20 mA output
setpoints.

Both Channel 1 and 2 can be pre-
cisely trimmed through the LCD
menu for precision applications.

The drawing shows the connections
for both outputs.

Wire Specification: 22 AWG 7/30,
insulation 0.010”

P6

54

P1

P4

P3

4

2 3

1

7 8 9

5 6

15

13

11 12 14

10

17

16

24
23

21

22

29
28

26
25

27

63

64

62

67

66

65

57

56

55

61

60

59

58

CH1 4-20mA -

CH1 4-20mA +

Primary Output

CH2 4-20mA -

CH2 4-20mA +

Secondary Output

31

30

52

53

51

Figure 3.7 Connections for the 4-20mA outputs

Note: Leave 4” to 6” slack for all
wires connected to the terminals of
P6. Slack required so that wires do
not interfere with opening or closing
of the front door.

Dwg# N104-39