Exhaust vent (pvc and abs vent), Exhaust vent (stainless steel vent), Installation – State 520 User Manual

Page 11

Advertising
background image

Installation 

11

Page

 

Excludes elbow termination, rain caps, or the 3” PVC Concentric Termination  

For details on the vent connection to the Direct Vent Indoor models, refer to P.14 

* For each elbow added, deduct 5 ft. from max. vent length.

 

‐Exhaust vent (PVC and ABS vent) ‐

 

 

The Direct Vent Indoor models can be connected with PVC or ABS venting (temperature rated up to 
149°F).  However, the manufacturer recommends PVC (or ABS) venting certified to ULC S636 standards.    

Item 

Material 

United States 

Canada 

Exhaust pipe and 

Fittings 

Schedule 40 PVC 

ANSI/ASTM D1785 

ULC S636 Certified 

Materials Only 

PVC‐DWV 

ANSI/ASTM D2665 

Schedule 40 CPVC 

ANSI/ASTM F441 

Schedule 40 ABS‐DWV

ANSI/ASTM D2661 

Pipe Cement/Primer

PVC 

ANSI/ASTM D2564 

CPVC 

ANSI/ASTM F493 

ABS 

ANSI/ASTM D2235 

NOTE: Do NOT Use Cellular Foam Core Pipe 

 The maximum length of exhaust vent piping must not exceed 50 ft. for 4” venting and 25 ft. for 

3” venting (deducting 5 ft. for each elbow used in the venting system).  Do not use more than 5 
elbows for 4” venting and 2 elbows for 3” venting.  

 When the horizontal vent run exceeds 5 ft., support the vent run at 3 ft. intervals with overhead 

hangers. 

 

Diameter 

Max. No. of Elbow 

Max. Vertical and Horizontal (Total) Vent Length

3” 

25 ft. 

4” 

50 ft. 

 

No. of Elbows 

Max. Vertical or Horizontal Length 

3” venting 

4” venting 

25 ft. 

50 ft. 

20 ft. 

45 ft. 

15 ft. 

40 ft. 

N/A 

25 ft. 

 
 
 
 
 

 

This is a Category IV appliance and must be vented accordingly. The vent system must be sealed air tight. 
All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed 
aluminum adhesive tape having a minimum temperature rating of 160°F. For best results, a vent system 
should be as short and straight as possible. 

 The Direct Vent Indoor models are a Category IV appliance and must be vented accordingly with 

any 4” vent approved for use with Category III/IV or Special BH type gas vent.  

The manufacturer recommends the “T‐Vent” line manufactured by TAKAGI (Refer to Takagi’s 

“T‐Vent” brochure for details). However, the following are also UL listed manufacturers: ProTech 
Systems Inc. (FasNSeal), Flex‐L Inc., Z‐Flex Inc. (Z‐Vent III), Metal‐Fab Inc., and Heat‐Fab Inc. (Saf‐
T Vent). 

Follow the vent pipe manufacturer’s instructions when installing the vent pipe. 