State 520 User Manual

Page 2

Advertising
background image

Contents 

2

Page

 

NOTE 

Check the rating plate to ensure this product matches your 
specifications.

 

In  accordance  with  ANZI  Z21.10.3,  CO  emission  does  not 
exceed 400 PPM for normal input.

 

 

 CONTENTS 

SPECIFICATIONS 

520 (T‐H2) and 320 (T‐H2S) models

 Gas

 Input

 

520 
(T‐H2) 
models

Natural 

Min:    13,000 Btu/h 

Max: 199,000 Btu/h 

Propane 

320 
(T‐H2S) 
models

Natural 

Min:    13,000 Btu/h 
Max: 180,000 Btu/h 

Propane 

Gas Connection

¾” NPT 

Water Connections

¾” NPT 

Condensate Drain Port 
Connection

½

” NPT 

Water Pressure*

15 ‐ 150 psi 

Natural Gas 
Inlet Pressure

Min. 5.0” WC  

Max. 10.5” WC 

Propane 
Inlet Pressure

Min. 8.0” WC  

Max. 14.0” WC 

Manif

o

ld

 Pressure**

 

520 Direct 
Vent Indoor  
(T‐H2‐DV)

Natural: 3.2” WC  

Propane: 5.5” WC 

520 Outdoor  
(T‐H2‐OS) 

Natural: 2.7” WC  
Propane: 4.6” WC 

320 Direct 
Vent Indoor  
(T‐H2S‐DV)

Natural: 2.5” WC  
Propane: 4.3” WC 

320 Outdoor  
(T‐H2S‐OS) 

Natural: 1.9” WC 
Propane: 3.6” WC 

Weight 

73 lbs.  
(Direct Vent Indoor models)
71 lbs. (Outdoor models)

Dimensions 

H25.6” x W18.5” x D12.4” 

Ignition

Electric Ignition 

Electric 

Supply

120 VAC / 60 Hz 

Consumption 

Operation of the  
Direct  Vent 
Indoor models 

152 W 
(1.27A) 

Operation of the 
Outdoor models 

102W
(0.85A)

Standby 

8.2 W

(0.07A)

Freeze‐
Protection 

207 W 
(1.73A) 

 
SPECIFICATIONS………………………………...
INTRODUCTION……………………………….…
SAFETY GUIDELINES…………….……………..
INSTALLATION………………………………..….
    General………………………………………..…
     Included Accessories…………………..…

Optional items…………………………..…..
Warning for Installations………..….....

     High‐altitude Installations………………

Installation for outdoor models……..
Installation for direct vent indoor 
models……………………………………………

    Venting Instructions…………………….... 
    Gas Supply / Gas Pipe Sizing………...… 
    Water Connections……………..……….…
    Pressure Relief Valve………………………
Condensate drain…………………………..
    Electrical Connections……………......... 
    Remote Controller Connection…….… 
    Pump Control Connections………..……
    Pump Control Mode…………………….…
    Easy‐Link System…………………………....
APPLICATIONS...…………………………………

Space Heating……….………….……………

INITIAL OPERATION..…………………….……
 
 
OPERATING SAFETY……………………………
NORMAL OPERATION…………………………

General………..……….………….……………
Temperature settings.…….…..…………
Flow……………………………………………….
Freeze Protection System…….…………
Maintenance and Service………………
Unit Draining and Filter Cleaning……

TROUBLESHOOTING……..……………………

General………..……….………….……………
Error codes.…………………….…..…………

COMPONENTS DIAGRAM………………..…
PARTS LIST………………….………………………
OUTPUT TEMPERATURE CHART……...…
LIMITED WARRANTY…………………….……

 










 
10
10
17
19
20
20
22
23
24
25
27
31
31
33
 
 
34
36
36
36
38
38
39
39
40
40
42
44
47
50
51

The manufacturer reserves the right to discontinue, or change at 
any time, specifications or designs without notice and without 
incurring obligations. 

Installation Manual 

Owner’s Guide

*40 psi or above is recommended for maximum flow. 
**The Manifold Pressure is the factory setting and generally 

should not need adjustment


Advertising