Additional clearances – State 520 User Manual

Page 16

Advertising
background image

Installation 

16

Page

 

‐Additional clearances ‐ 

Please follow all local and national codes in regards to proper termination clearances.  In the absence of 
such codes, the following clearances can be used as guidelines.  Local codes supersede these guidelines.  

For sidewall terminations  

 

Exhaust termination

1ft. 

1ft. 

2ft. 

Inside 
corner 

For multiple sidewall exhaust 
terminations (e.g. multi‐unit 
systems), an exhaust termination 
must be at least 1 ft. away from 
another exhaust termination.  An 
exhaust termination must also be 
at least 2 ft. away from an inside 
corner (if the adjacent wall is less 
than 2 ft. of length, the minimum 
required distance away from the 
inside corner will be equal to the 

length of that adjacent wall).       

For direct‐vent sidewall 
terminations that use two 
separate penetrations for the 
intake and exhaust, distance 
the intake and exhaust 
terminations at least 3 ft. away 
from each other, no matter the 

orientation.       

For multiple‐unit, direct‐vent sidewall 
terminations that combine the intake 
and exhaust into a single penetration, 
space each direct‐vent termination at 
least 1 ft. away from each other, no 
matter the orientation.  A direct‐vent 
termination must also be at least 2 ft. 
away from an inside corner (if the 
adjacent wall is less than 2 ft. of 
length, the minimum required 
distance away from the inside corner 
will be equal to the length of that 
adjacent wall).           

For multiple‐unit rooftop terminations (whether for standard indoor or 
direct‐vent installations) space all exhaust and intake terminations in 
accordance with local codes.  An exhaust termination must be spaced from 
a wall or surface in accordance with local codes as well.  In the absence of 
such a code, an exhaust termination must be a horizontal distance of at 

least 2 ft. away from a wall or surface.           

A: in accordance with local codes 

For rooftop terminations

 

Air intake 

Exhaust termination

 A 

A

A

2ft. 

Air intake 

Exhaust 
termination 

Exhaust and/or direct‐vent 
sidewall terminations should 
be at least 2 ft. away from an 
opposite surface/wall.  Do 
not place the termination 
directly in front of an 
opening into a building.   

2ft. 

Exhaust 
termination 

Air supply inlet

3ft.

3ft.

3ft.

Direct vent termination 

1ft. 

1ft. 

Inside 
corner 

2ft.