Stainless steel venting illustrations, Installation – State 520 User Manual

Page 14

Advertising
background image

Installation 

14

Page

 

1. Connect a 4” PVC Straight pipe directly on the intake vent collar of the water heater. 
2. Connect a 4x3” PVC reducer to the 4” PVC Straight pipe. 
3. From the reducer, continue on the rest of the vent run with 3” PVC pipe. 

(For Intake: 4” only) 

(For Intake: 3” only) 























   

 























 Regarding the clearances from the exhaust terminator to 

the air inlet or opening, refer to the next few pages. 

 Follow all vent system manufacturer’s instructions and all 

local codes.  

 Do  not  common  vent  or  connect  any  vent  from  other 

appliances to the Direct Vent Indoor models vent. 

 Use  4”  Category  III/IV  approved  or  Special  BH,  single  or 

double wall stainless steel vent pipe. 

Vertical Installation Diagram 

Horizontal Installation Diagram 

*PVC adaptor is included with the Direct Vent Indoor models. 

4” vent connection Diagram

3” vent connection Diagram 

‐Stainless steel Venting Illustrations‐

 

1.  Connect a 4” PVC Straight pipe directly on the intake vent collar of the water heater. 

Roof Flashing

Roof

Rain Cap 

Fire stop

Wall

Sidewall Vent
Terminator 

Exhaust vent collar 
of the Direct Vent 
Indoor models 
(Female) 

 

PVC adaptor* 

4” PVC coupler

4” PVC Straight pipe 

4” PVC Straight 
pipe 

Intake vent collar 

 

3” PVC Straight pipe 

4x3” PVC reducer

PVC adaptor* 

3” PVC Straight 
pipe 

4x3” PVC reducer 

4” PVC Straight 
pipe 

Intake vent collar 

Exhaust vent collar 
of the Direct Vent 
Indoor models 
(Female) 

 