‐Natural Gas Supply Piping‐ 

Maximum Delivery Capacity of Cubic Feet of Gas per Hour of IPS Pipe Carrying Natural Gas of 0.60 Specific Gravity 
Based on Pressure Drop of 0.5” WC 

 

Based on Energy Content of 1,000 BTU/Cubic Ft.: The water heater requires 199 Cubic Ft./hr for the 520 (T‐H2) 
models, and 180 Cubic Ft./hr for the 320 (T‐H2S) models.  
 

                  

Unit: Cubic Feet per Hour 

Pipe Size 

Length 

Diameter 

10’ 

20’ 

30’ 

40’ 

50’ 

60’ 

70’ 

80’ 

90’ 

100’ 

125’ 

150’

200’

¾” 

363 

249 

200 

171 

152 

138 

127 

118 

111 

104 

93 

84 

72 

1” 

684 

470 

377 

323 

286 

259 

239 

222 

208 

197 

174 

158

135

1 ¼” 

1,404 

965 

775 

663 

588 

532 

490 

456 

428 

404 

358 

324

278

1 ½” 

2,103  1,445 1,161 

993

880

798

734

683

641

605 

536 

486

416

2” 

4,050  2,784 2,235  1,913 1,696 1,536 1,413 1,315 1,234  1,165  1,033

936

801

‐Propane (LP) Gas Supply Piping‐ 

Maximum Capacity of Propane (LP) Gas Based on 11” WC supply pressure at a 0.5” WC pressure drop 

Unit: kBTU per Hour 

Pipe Size 

Length 

Diameter  10’ 

20’ 

30’ 

40’ 

50’ 

60’ 

70’ 

80’ 

90’ 

100’ 

125’ 

150’

200’ 

¾” 

567 

393 

315 

267 

237 

217 

196 

185 

173 

162 

146 

132 

112 

1” 

1,071 

732 

590 

504 

448 

409 

378 

346 

322 

307 

275 

252 

213 

1 ¼” 

2,205  1,496  1,212  1,039 

913 

834 

771 

724 

677 

630 

567 

511 

440 

1 ½” 

3,307  2,299  1,858  1,559  1,417 1,275 1,181 1,086 1,023

976 

866 

787 

675 

2” 

6,221  4,331  3,465  2,992  2,646 2,394 2,205 2,047 1,921 1,811  1,606  1,496

1,260

 

For more information, please see the next page. 
 



















 

Based on Energy Content of 1,000BTU/Cubic Ft: 
 
Divide each appliance’s BTU requirement by 1,000BTU to get 
the appliances Cubic Ft. requirement. 
 
Take into account the distance the appliance is from the gas 
meter, look in the above gas chart to properly size the line. 

 
For sections of the gas line supplying gas to more than one 
appliance (Ex: Point A to Point B), add up the cubic ft. 
requirements of the appliances that are being supplied by that 
section, and size to the farthest appliance. 
 
For Example: The section from A to B supplies gas to the 
furnace, range, and dryer. Adding up the BTU requirements 

and dividing by 1,000 yields a cubic ft. requirement of 220 
cubic ft. of gas. The farthest appliance is the range, which is 50 
ft. away from the meter. Looking at the above chart, and 
under the column of 50ft., Section A to B needs to be 1” in 
order to supply 220 cubic ft. 

Range 

65,000BTU 

C

10’ Length 

1” Pipe Size 

Gas Sizing Example 

(Natural Gas) 

10’ Length 

3/4” Pipe Size 

15’ Length 

1/2” Pipe Size 

10’ Length 

1/2” Pipe Size 

Furnace 

120,000BTU 

Water Heater 

5’ Length 

1‐1/4” Pipe Size 

10’ Length 

3/4” Pipe Size 

Dryer 

35,000BTU

15’ Length 

1” Pipe Size 

5’ Length 

1‐1/4” Pipe Size 

Gas Meter 

B

A

199,000BTU 
          or  
180,000 BTU 