‐Condensate Drain Connections‐

 

 
 
 
 

The water heater models are high efficiency condensing water heaters that produce condensate (acidic 
water).  The acidic condensate generated in the secondary heat exchanger can be neutralized by the 
Neutralizer accessory. 
 
Case A: If a neutralizer is not required 
1. Connect a 1/2” FPT X 3/8” (or 1/2”) HB Adaptor to the condensate drain port at the bottom of the 

water heater. 

2. Connect a condensate drain tube to the 1/2” FPT X 3/8” (or 1/2”) HB Adaptor. The manufacturer 

recommends the material of the condensate tube be either EPDM or PVC. 

3. Leave an adequate amount of space between the end of the drain tube and the actual drain, to 

facilitate proper drainage. 

 
Case B: If a neutralizer is required (installing the Neutralizer assembly) 
1. Connect the 1/2” FPT X 3/8” MPT Adaptor to the condensate drain port at the bottom of the water 

heater. 

2. Connect the Neutralizer to the 3/8” MPT connection of the adaptors.  There is a flow direction 

indicator on the neutralizer.  Please orient the neutralizer in the proper direction. 

3. Connect a 1/2” drain tube to the other end of neutralizer. 
4. Leave an adequate amount of space between the end of the drain tube and the actual drain, to 

facilitate proper drainage.  

 
 

WARNING 

Discharge condensate (acidic water) in accordance with all local codes and 
common safety practices.

Neutralizer cartridge
(Included with 
Neutralizer accessory) 

1/2” Condensate 
drain tube 

3/8” or 1/2” 
Condensate 
drain tube 

Case A 

Adequate space 

Drain 

Case B 

Condensate 
drain port 

1/2”FPT X 3/8” 
(or 1/2”) HB 

Condensate 
drain port 

1/2”FPT X 3/8”MPT
(Included with 
Neutralizer accessory) 

Adequate space

Drain

3/8”MPT X 1/2”HB
(Included with 
Neutralizer accessory) 