In an Easy‐Link system, the pump must be connected to the “Pump connector” in 
the “PARENT unit” only. 
If the pump is connected to any of the “CHILD units”, the 
pump will not work. 

PUMP CONTROL CONNECTIONS 

The water heater can be used to control a recirculation pump. Proper pump control helps to preserve 
the life of the system and saves energy as well

 
The water heater pump control port is a “normally open dry contact”, and therefore needs additional 
components  to  properly  control  a  recirculation  pump.  To  control  a  recirculation  pump,  connect  the 
pump  to  the  “Pump  connector”  in  the  water  heater  as  shown  in  the diagram  below.  (In  an  Easy‐Link 
system,  connect  the  pump  ONLY  to  the  “PARENT”  unit.)  The  pump  is  to  be  connected  using  suitable 
relays shown in the diagram below.  
Please make sure the relays are properly rated for the recirculation pump.  
Using the water heater’s internal thermistors as a temperature control, the recirculation pump will only 
turn on when recirculation is needed. 

 
 
 







 

CAUTION 

Connect to this “Pump connector”.

Rec

irculation

 

pump

 

Power supply 
for pump 
120 VAC 
220 VAC etc 

Power supply 

 for relay 

These components are NOT included with the water heater and 
are external to the unit.  They must be acquired separately. 

Thermal  

relay 

120 VAC 
220 VAC etc 
for relay 