Operation Pressure Object

User can set current atmospheric pressure to improve the calculation

accuracy of pressure dependent humidity parameters.

Table 33

Operation Pressure Object Properties

Property

Data type

Writable

Value or Initial Value

Object Identifier

BACnet Object Identifier

No

00 80 00 01 (hex)

Object Type = 2,

Instance = 1

Object Name

Character String

No

"OPER P"

Object Type

BACnet Object Type

No

2 (Analog Value)

Present Value

Real

Yes

1013.25

Description

Character String

No

"Operation Pressure"

Units

BACnet Engineering Units

No

133 (hectopascals)

Status Flags

BACnet Status Flags

No

0 (FAULT == FALSE)

Event State

BACnet Event State

No

0 (NORMAL)

Out of Service

BOOLEAN

No

0 (FALSE)

Present Value

Two pressure related objects (Pressure and Altitude) are linked together.

If Present Value in object is changed by user, Present Value in another

object is changed accordingly.

Status Flags

Table 34

Status Flags

Flag

State

Cause

IN_ALARM

FALSE

Always FALSE

FAULT

FALSE

Always FALSE

OVERRIDDEN

FALSE

Always FALSE

OUT_OF_SERVICE

FALSE

Always FALSE

Event State

Event State value is always NORMAL.

Out of Service

Out of Service value is not writeable.