Table 16 inputs and outputs, Table 17 mechanics – Vaisala HMW90 User Manual

Page 86

Advertising
background image

User's Guide _______________________________________________________________________

84 ___________________________________________________________________ M211399EN-F

Table 16

Inputs and Outputs

Property

Description / Value

HMW92 and TMW92

Outputs

HMW92

2 x 4 ... 20 mA, loop powered

TMW92

1 x 4 ... 20 mA, loop powered

Loop resistance

0 ... 600 Ω

Supply voltage

20 ... 28 VDC at 500 Ω load

10 .... 28 VDC at 0 Ω load

Isolation between output channels 500 VDC

HMW93 and TMW93

Outputs

HMW93

2 x 0 ... 5V, 0 ... 10 V

TMW93

1 x 0 ... 5V, 0 ... 10 V

Load resistance

10 kΩ min.

Supply voltage

18 ... 35 VDC

24 VAC ±20 % 50/60 Hz

Max. current consumption

12 mA

max. with relay 25 mA

Relay

1 pc (SPST, max. 50 VDC, 500 mA)

3-wire installation max cable

resistance

2.5 Ω at 24V supply

(with 10 V output, relay not used)

HMW95

Supply voltage

18 ... 35 VDC

24 VAC ±20 % 50/60 Hz

Current consumption (with

termination)

Average

10 mA at 24 VDC

Maximum

30 mA at 24 VDC

Power consumption

< 0.3 W

Output type

RS-485 (galvanic isolation, 1.5 kV)

RS-485 end of line termination

Enable with jumper, 120 Ω

Supported protocols

Selectable by DIP switch

BACnet MS/TP

Operating mode

Selectable Master/Slave

Address range, master mode 0 ... 127

Address range, slave mode 128 ... 255

Modbus RTU

Address range

0 ... 247

Service port

RS-485 line

for temporary service use

Table 17

Mechanics

Property

Description / Value

IP class

IP30

Standard housing color

White (RAL9003*)

Optional housing colors

(configurable models only)

Black (RAL9005*)

Grey (RAL7035*)

Light Ivory (RAL1015*)

Housing material

ABS/PC, UL-V0 approved

Output connector

Screw terminals

max. wire size 2 mm

2

(AWG14)

Service port connector

4-pin M8

Weight

155 g

Advertising