Channel 2 now behaves like this:

- Clipping is now set to 10%, meaning the output is allowed to vary

between 0.6 ... 5.4 V. The channel will output the measurement for

-11 ... 61 °C, but range 1 ... 5 V remains scaled to show -5 ... 55 °C.

- Error limit is 20%, which means channel 2 will show the error state

(6 V) when the measured value is 20% outside the scaled output

range. With the settings above, this will happen if the measured

temperature is outside range -17 ... 67 °C.

- The output will never actually be between 5.4 and 6.0 V because of

clipping.

Display Settings

Select Parameters to Display

Use the DSEL command to select the parameters that are displayed on

the transmitter screen. You can select parameters by abbreviation, or

select same parameters as are assigned to the analog outputs. If only one

parameter is selected, it is shown vertically centered on the transmitter

screen.
DSEL [Q1 Q2 Q3]<cr>

where
Q1 = First parameter to show on the screen. Available parameters

are:

out1 Same parameter as analog output channel 1

out2 Same parameter as analog output channel 2

RH relative humidity

T

temperature

Tdf dew/frost point temperature

Td

dew point temperature

Tw

wetbulb temperature

h

enthalpy

x

mixing ratio

a

absolute humidity

dTd

dew/frost point depression

Q2 = Second parameter to show on the screen. Available

parameters are the same as for Q1.

Q3 = Third parameter to show on the screen. Available parameters

are the same as for Q1.