Reset Transmitter

Use the RESET command to reset the transmitter.

RESET<cr>
Example:

>reset

Resetting

HMW93 / 1.00.00.0000 / XM90

>

Set BACnet Parameters

Use the BACNET command to show or set some of the transmitter’s

BACnet parameters. You can also use the BACNET command to

reinitialize the BACnet stack of the transmitter without having to reset or

power cycle the transmitter.

BACNET [parameter_name [parameter_value]] [reinit]<cr>

where
parameter_name = Name of the BACnet parameter to change. Available

parameters are:

Instance: BACnet instance number. Unsigned

(0 ... 4194302).

Name: BACnet Object_Name shown in the Device

object. String, no spaces.

Description: BACnet Description shown in the

Device object. String, no spaces.

Location: BACnet Location shown in the Device

object. String, no spaces.

Password: Password used in ReinitializeDevice

service. String, no spaces.

MAX_MASTER: Max_Master parameter in Device

object. Unsigned (0 ... 127)

parameter_value = New value of the parameter. See descriptions above

for allowed values.

reinit

= Reinitializes the BACnet stack. Must be given as the

only argument for the BACNET command.