User's Guide _______________________________________________________________________

92 ___________________________________________________________________ M211399EN-F

Protocol_Services

Who-Is, I-Am, Who-Has, I-Have and UnconfirmedCOVNotification

services are available only when HMW90 is MS/TP master. Reinitialize

Device service must be password protected. According to BACnet

protocol, password is character string having max 20 characters. Default

password is "1234". Password can be changed through the service port

by using the BACNET command. See section Set BACnet Parameters on

page 64.

Database_revision

This is changed during operation according to section 12.11.35 of

ANSI/ASHRAE standard 135-2008.

Relative Humidity object

This Analog Input Object exists only in the HMW95 model.

Table 20

Relative Humidity Object Properties

Property

Data type

(Application Type)

Writable

(Conformance

Code)

Value or Initial Value Persistence

Object_Identifier BACnetObjectIdentifier No (R)

00 00 00 02 (hex)

Object Type = 0,

Instance = 2

Nonvolatile

Object_Name

CharacterString

No (R)

"RH"

Nonvolatile

Object_Type

BACnetObjectType

(ENUMERATED)

No (R)

0 (Analog Input)

Fixed

Present_Value

Real

Yes

(When Oos)

(R)

0.0

Volatile

Description

CharacterString

No (O)

"Relative Humidity"

Nonvolatile

Units

BACnetEngineeringUnits

(ENUMERATED)

No (R)

29 (percent-relative-

humidity)

Nonvolatile

Status_Flags

BACnet Status Flags

(BIT STRING)

Yes (when

OoS) (R)

0 (FAULT == FALSE) Volatile

Reliability

BACnet Reliability

(ENUMERATED)

Yes (when

OoS) (O)

0 (NO FAULT

DETECTED)

Volatile

Event State

BACnetEventState

(ENUMERATED)

No (R)

0 (NORMAL)

Volatile

Out_of_Service BOOLEAN

Yes (R)

0 (FALSE)

Volatile

COV_Increment Real

Yes (O)

NaN (COV reporting

disabled)

Nonvolatile

Min_Pres_Value Real

No (O)

0.0 (same as limit for

UNDER_RANGE)

Nonvolatile

Max_Pres_Value Real

No (O)

100 (same as limit for

OVER_RANGE)

Nonvolatile

Advertising