Relay configuration in dip mode – Vaisala HMW90 User Manual

Page 25

Advertising
background image

Chapter 3 ________________________________________________________________ Installation

VAISALA ________________________________________________________________________ 23

If you change the position of DIP switch 8, note the following:

- When changing from Custom to DIP: Current custom settings are

overwritten by the settings from the DIP switches at next power up.

Settings that do not have DIP switches remain unchanged, except for

display layout (DSEL command) that is set to default.

- When changing from DIP to Custom: The DIP settings that were

used when the power was last on are carried over to the custom

settings at next power up.

Relay Configuration in DIP Mode

NOTE

Relay is included on HMW93 and TMW93 transmitters only.

When the transmitter is configured using DIP switches, the functioning

of the relay is configured by DIP switch 5 and the rotary switch on the

component board:

- DIP switch 5 determines if the relay is closed above or below the

setpoint.

- The position of the rotary switch determines the setpoint according to

the table below.

Table 5

Rotary Switch and Relay Setpoint

Rotary Switch Position Setpoint on HMW93

Setpoint on TMW93

0

5 %RH

0 °C (32 °F)

1

10 %RH

5 °C (41 °F)

2

20 %RH

10 °C (50 °F)

3

30 %RH

15 °C (59 °F)

4

40 %RH

20 °C (68 °F)

5

50 %RH

25 °C (77 °F)

6

60 %RH

30 °C (86 °F)

7

70 %RH

35 °C (95 °F)

8

80 %RH

40 °C (104 °F)

9

90 %RH

45 °C (113 °F)

NOTE

The rotary switch only has 10 positions. Do not turn the switch so that it

is between two positions.

Advertising