User's Guide _______________________________________________________________________

106 __________________________________________________________________ M211399EN-F

Status Registers (Read-Only)

Table 43

HMW90 Modbus Status Registers

Name

Address

Description

Error code (bits 15…0)

0513,6913 0 = no errors

Configuration Registers

Configuration parameter registers are used to configure the measurement.

Writing out-of-range values is silently ignored.

NOTE

Elevation is linked to pressure according to the following equation:
p = 101325 (1 - 2.25577 10

-5

h)

5.25588

where p is pressure in Pa and h is altitude above sea level in m. This

means that changing altitude will also change pressure and vice versa.

Table 44

HMW90 Modbus Configuration Parameter Registers

Name

Metric float Metric

integer

Metric unit &

valid range

Non-metric

float

Non-metric

integer

Non-metric unit

& valid range

Pressure 0777…0779 1029 (×1) 700…1100 hPa 7177…7179 7429 (×1)

700 … 1100 hPa

Elevation 0779…0780 1030 (×1) -700...2300 m 7179…7180 7430 (×1)

-2300 … 10000 ft