Appendix A _________________________________________________________ BACnet Reference

VAISALA ________________________________________________________________________ 97

Status Flags

Table 30

Status Flags

Flag

State

Cause

IN_ALARM

FALSE

Event State equals 0 (NORMAL)

TRUE

Event State not 0

FAULT

FALSE

Reliability equals 0 (NO FAULT

DETECTED)

TRUE

Reliability not 0

OVERRIDDEN

FALSE

Always FALSE

OUT_OF_SERVICE FALSE

Present Value may NOT be written

via BACnet

TRUE

Present Value may be written via

BACnet

Reliability

Reliability of calculated humidity objects depends on reliability of RH

measurement.

Table 31

Reliability

State

Cause

0 NO_FAULT_DETECTED

1 NO_SENSOR

No contact to measurement module

2 OVER_RANGE

RH over 100%

3 UNDER_RANGE

RH under 0%

7 UNRELIABLE_OTHER

Other measurement error

Event State

Table 32

Event State

State

Cause

0 NORMAL

Reliability equals 0 (NO FAULT

DETECTED)

1 FAULT

Reliability not 0

Out of Service

Out of Service value is writeable. By Default = FALSE. Parameter is

volatile.