Status flags, Reliability, Event state – Vaisala HMW90 User Manual

Page 95: Out of service

Advertising
background image

Appendix A _________________________________________________________ BACnet Reference

VAISALA ________________________________________________________________________ 93

Status Flags

Table 21

Status Flags

Flag

State

Cause

IN_ALARM

FALSE

Event State equals 0 (NORMAL)

TRUE

Event State not 0

FAULT

FALSE

Reliability equals 0 (NO FAULT

DETECTED)

TRUE

Reliability not 0

OVERRIDDEN

FALSE

Always FALSE

OUT_OF_SERVICE FALSE

Present Value may NOT be written

via BACnet

TRUE

Present Value may be written via

BACnet

Reliability

Table 22

Reliability

State

Cause

0 NO_FAULT_DETECTED

1 NO_SENSOR

No contact to measurement module

2 OVER_RANGE

RH over 100%

3 UNDER_RANGE

RH under 0%

7 UNRELIABLE_OTHER

Other measurement error

Event State

Table 23

Event State

State

Cause

0 NORMAL

Reliability equals 0 (NO FAULT

DETECTED)

1 FAULT

Reliability not 0

Out of Service

Out of Service value is writable. By Default = FALSE.