List of serial commands – Vaisala HMW90 User Manual

Page 43

Advertising
background image

Chapter 4 _________________________________________________________________ Operation

VAISALA ________________________________________________________________________ 41

List of Serial Commands

Some commands, such as RSEL, are not available if the required feature

is not present on the transmitter, or the command is not relevant.

All commands can be issued either in uppercase or lowercase. In the

command examples, the keyboard input by the user is in bold type.

The notation <cr> refers to pressing the carriage return (Enter) key on

your computer keyboard. Enter a <cr> to clear the command buffer

before starting to enter commands.

Table 7

Basic Serial Commands

Command

Description

?

Show transmitter information.

CALCS

Show all measured and calculated parameters.

ECHO

Show or set remote echo mode.

ENV

Show or set environmental parameters.

ERRT

Show error table.

ERRS

Show currently active errors.

FORM [modifier string]

Show or set output format.

HELP

Show list of currently available serial commands.

INTV [0 ... 9999 s/min/h] Set continuous output interval for R command.

PASS [9000]

Access advanced serial commands.

R

Start the continuous outputting.

RESET

Reset the transmitter.

S

Stop the continuous outputting.

SDELAY [0 ... 255]

Show or set serial line transmission delay in

milliseconds.

SEND

Output measurement message once.

SNUM

Show transmitter serial number.

STATUS

Show transmitter status.

UNIT [m/n]

Select metric or non-metric units.

VERS

Show transmitter firmware version.

Table 8

Advanced Serial Commands

Command

Description

AMODE

Show or set analog output mode.

AOVER

Show or set analog output overrange and clipping

behavior.

ASEL

Show or set analog output parameter.

ATEST

Test analog putput.

BACNET

Show or set BACnet parameters.

CDATE

Show or set calibration date.

CRH

Calibrate and adjust RH measurement.

CT

Calibrate and adjust T measurement.

CTEXT

Show or set calibration information.

DSEL

Select parameters to display on screen.

FRESTORE

Restore transmitter to factory settings.

RMODE

Show or set relay operation mode.

RSEL

Show or set relay parameter and limits.

RTEST [open/closed]

Test relay operation.

Advertising