Appendix A _________________________________________________________ BACnet Reference

VAISALA ________________________________________________________________________ 91

Property

Data type

(Application Type)

Writable

(Conforma

nce Code)

Value or Initial Value

Persistence

Object_List

BACnetARRAY[N]of

BACnetObjectIdentifier

N (R)

Device Object

AI2 (Relative Humidity)

AI3 (Temperature)

AI4 (Dewpoint)

AI5 (Dewpoint (Tdf))

AI6 (Dewpoint

depression)

AI7 (Wet bulb

temperature)

AI8 (Absolute humidity)

AI9 (Mixing ratio)

AI10 (Enthalpy)

AV1 (Pressure)

AV2 (Altitude)

Fixed

Max_APDU_Length_

Accepted

Unsigned16

N (R)

244

Fixed

Max_Master

Unsigned16 (0..127)

Y (R/O)

127

Nonvolatile

Max_Info_Frames

Unsigned

N (R/O)

1

Fixed

Segmentation_Suppo

rted

BACnetSegmentation

(ENUMERATED)

N (R)

3 (No segmentation)

Fixed

APDU_Timeout

Unsigned

N (R)

3000 (ms)

Fixed

APDU_Retries

Unsigned

N (R)

0

Fixed

Device_Address_Bin

ding

List of

BACnetAddressBindin

g

N (R)

NULL

Fixed

Database_Revision

Unsigned

N (R)

0

Volatile

Object_Identifier

Must be unique in BACnet network. As Object Identifier is 22 bits long

its value range is 0 ... 4194303. Each device is assigned a random value

in this range at Vaisala factory.

Object_Name

Must be unique in BACnet network. Default object name contains the

name and serial number of the device. For example:

- Device model is HMW95, with serial number G1234567.
- Object_Name is "HMW95_G1234567".

System_Status

System status can be OPERATIONAL (0) or NON-OPERATIONAL (4).

Device goes to NON-OPERATIONAL state in case of fatal error.