Dip switches of digital output models, Figure 9, Dip switch settings of digital output models – Vaisala HMW90 User Manual

Page 28

Advertising
background image

User's Guide _______________________________________________________________________

26 ___________________________________________________________________ M211399EN-F

DIP Switches of Digital Output Models

1209-016

Figure 9

DIP Switch Settings of Digital Output Models

DIP

Position

Setting

1

Modbus

Modbus protocol in use.

BACnet

BACnet protocol in use.

2 ... 4

A

B

C

Serial line baud rate.

Off

Off

Off Automatic (default).

Off

Off

On 4800 (not available with BACnet protocol)

Off

On

Off 9600

Off

On

On 19200

On

Off

Off 38400

On

Off

On 57600

On

On

Off 76800

On

On

On 115200

5

Parity Even

Parity even.

Parity None

Parity none.

6

Non-Metric

Use non-metric units on display and service

port. No effect on Modbus and BACnet.

Metric

Use metric units on display and service port.

No effect on Modbus and BACnet.

7

Not used

8

Not used

NOTE

If the serial line baud rate is set to Automatic, the transmitter attempts to

determine the baud rate of the traffic in the RS-485 network. The

transmitter cycles through all baud rate choices, listening for 10 seconds

at each rate. When it detects valid RS-485 traffic, it remains at the

detected baud rate until it is reset or power cycled.

NOTE

The parity setting is only relevant for Modbus protocol, in which it

chooses between 8N2 (parity none) and 8E1 (parity even) formats.

1

ON

2 3 4 5 6 7 8

Modbus

BACnet

Parity Even

A B C

Parity None

Baud

Rate

1 2 3 4 5 6 7 8

HMW95

128 64 32 16 8 4 2 1

Address

(Binary Weighting)

ON

Metric

Non-Metric

Advertising