SECTION 5 - JLG CONTROL SYSTEM

5-8

– JLG Lift–

3121166

5.5

ELEVATION SENSOR CALIBRATION

NOTICE

MACHINE MUST BE ON LEVEL GROUND BEFORE ELEVATION SEN-
SOR CAN BE SET.

1.

Be sure that the machine is parked and stowed on
level ground.

2.

Attach the analyzer near the ground control sta-
tion.

3.

Go to Access Level 1 and scroll through to CALI-
BRATION.

4.

Under Calibrations, go to SET ELEV SENSOR.

5.

Press enter for Yes and the Elevation Sensor will
set.

NOTE: Check the elevation sensor by lifting the scissor arms,

from the platform, and driving until the drive speed
cuts back. Refer to Table 1-13, High Drive Speed Cut-
out Height
for proper speed cut out height.

5.6

UPDATING SOFTWARE

Updating the ground module software requires a laptop
computer, connecting cable, and software update cd.
Contact JLG Industries to acquire the software cd.

Before updating the software, use the Hand-held Ana-
lyzer to view the machine’s settings (MACHINE SETUP
and PERSONALITIES) (refer to Figure 5-2. thru Figure 5-4.
for Analyzer Flow Chart). It is important to write down
the settings to verify they are the same after software
update is complete.

NOTE: Software update must be done with the machine

powered in Ground Mode.

1.

Disconnect analyzer from diagnostic port.

2.

Using the laptop connector cable, connect the lap-
top to the diagnostic port.

3.

Run the software update cd.

a. When the JLG Reprogramming Tool dialogue

box appears, click on the Program button.

b. Another dialogue box will appear asking if you

want to overwrite the current software version.
Click YES.

4.

After software update is complete, disconnect
computer from diagnostic port.

5.

Reconnect the hand-held analyzer to the diagnos-
tic port.

a. Enter Access Level 1 password; 33271

b. Scroll to MACHINE SETUP. Change MODEL

NUMBER to a different model, but immediately
change it back to the proper setting. Do the
same for MARKET. This will ensure the settings
are carried over to all parameters.

c. Scroll through the settings to verify they are

the same as before the software update.

6.

Disconnect Analyzer.

7.

Software update is complete.