SECTION 6 - DIAGNOSTIC TROUBLE CODES

3121166

– JLG Lift –

6-7

224

FUNCTION PROBLEM -
STEER LEFT PERMA-
NENTLY SELECTED

The steer left switch was closed
during power-up in platform
mode.

• Check if the steer left switch is obstructed or jammed.
• Check steer left switch and its wiring. The steer left

switch input (24V) is from platform board terminal J1-
1, and its output (24V when closed) is to platform
board terminal J1-15.

• Replace platform board.

225

FUNCTION PROBLEM -
STEER RIGHT PERMA-
NENTLY SELECTED

The steer right switch was
closed during power-up in plat-
form mode.

• Check if the steer right switch is obstructed or

jammed.

• Check steer right switch and its wiring to the platform

board. The steer right switch input (24V) is from plat-
form board terminal J1-1, and its output (24V when
closed) is to platform board terminal J1-16.

• Replace platform board.

226

ACCELERATOR FAULTY -
WIPER OUT OF RANGE

The joystick signal is outside the
acceptable range of 0.50V - 4.5V,
or is unstable.

• Center joystick and check to see if a power cycle will

clear DTC.

• Check the joystick signal and its wiring. The joystick

input (5V) is from the platform board terminal J1-5, its
output (2.5V with joystick at center) to the platform
board terminal J1-6, and its ground (0V) is to the plat-
form board terminal J1-7. Observe output signal while
slowly operating joystick.

• Replace platform board.

227

STEER SWITCHES
FAULTY

The steer left and steer right
inputs were closed simultane-
ously.

• Check if the steer switches are damaged, obstructed

or jammed.

• Check the steer switch signals and wiring to the plat-

form board. The steer switch input (24V) is from plat-
form board terminal J1-1, outputs (24V when closed)
are to platform board terminals J1-15 and J1-16 (left
and right).

• Replace platform board.

228

FUNCTION LOCKED
OUT - ACCELERATOR
NOT CENTERED

The joystick was not centered at
power-up.

• Release joystick and allow to center.
• Check if the joystick is obstructed or jammed.
• Check the joystick signal and its wiring. The joystick

input (5V) is from the platform board terminal J1-5, its
output (2.5V with joystick at center) to the platform
board terminal J1-6, and its ground (0V) is to the plat-
form board terminal J1-7. Observe output signal while
slowly operating joystick.

• Replace platform board.

229

FUNCTION PROBLEM -
TRIGGER PERMA-
NENTLY CLOSED

The trigger switch was closed
during power-up in platform
mode.

• Check if the trigger switch is obstructed or jammed.
• Check the trigger switch signal and wiring to the plat-

form board. The trigger input (24V) is from platform
board terminal J1-1, and its output (24V when closed)
is to platform board terminal J1-8.

• Replace platform board.

2210 TRIGGER CLOSED TOO

LONG WHILE IN NEU-
TRAL

The trigger switch was closed for
more than five seconds while
the joystick was centered.

• Check if the trigger switch is obstructed or jammed.
• Check the trigger switch signal and wiring to the plat-

form board. The trigger input (24V) is from platform
board terminal J1-1, and its output (24V when closed)
is to platform board terminal J1-8.

• Replace platform board.

2-2 Platform Controls

DTC

FAULT MESSAGE

DESCRIPTION

CHECK