6010 Series Operations Manual

Rev E 2/14/2012

Page 33 of 68

Set the Scale Low value to correspond with the minimum value of the process

output in electrical units. For 0-5V, set to 0. For 1-5V, set to 1. For 4-20mA, set

to 4.

Set the Scale High value to correspond with the maximum value of the process

output in electrical units. For 0-5V, set to 5. For 1-5V, set to 5. For 4-20mA, set

to 20.

Set the Range Low value to the minimum temperature (or humidity) that will

correspond with the Scale Low value (default is 0.0).

Set the Range High value to the maximum temperature (or humidity) that will

correspond with the Scale High value (default is 100.0).

6. If an offset (or calibration) is needed, adjust the o.CA parameter accordingly

7. Press and hold the infinity button for 2 seconds to exit to home page

Once all changes are made refer to Section 14 to relock the controllers.