6010 Series Operations Manual

Rev E 2/14/2012

Page 34 of 68

Ramp & Soak:

A ramp and soak control system is included with DLUX301 & DLUX302 controllers. This

allows the user to store up to 40 steps spanning 4 profiles. A step consists of a change

in set-point (or ramp). Another step is used to maintain a set-point for a fixed duration

(or soak). Steps can also be repeated any number of times.

The temperature and humidity control systems are independent. Temperature can run

through a profile while humidity is maintained constant and visa versa. By starting the

temperature and humidity profile together, the controls can run in-sync.

Starting / Stopping a Profile

Once a profile is programmed into the controller, it may be started or stopped at any

time from the home page.

1. Press the ADVANCE button several times until P.St1 appears

2. Use the UP or DOWN arrow keys to choose the file or step number within a profile

where you want to begin running

3. Press the ADVANCE button one time; P.AC1 should display

4. Select the appropriate action with the UP & DOWN arrow keys:

Parameter Description

Display

No action

nonE

Begin execution from first step of the specified profile number

ProF

Pause the currently running profile

PAUS

Resume running the profile from the previously paused step

rESU

End the profile

End

Begin running the profile from the specified step number

StEP

See Appendix A for an example of a Ramp & Soak profile.