Auto-tuning control panel – MTS Series 793 User Manual

Page 240

Advertising
background image

Description

Item

From any integrator mode, the local integrator will turn off when system
hydraulics are turned off.

Auto-High—Turns on the local integrator when hydraulics are set to High.

Auto-Low—Turns on the local integrator when hydraulics are set to Low.

You must have Tuning access level to modify this control.

Integrator Inhibit

This control displays all digital inputs in a dropdown list. You can select
any digital input in order to determine when a control mode's integrator
turns on.

When a digital input is selected, it determines when the integrator for that
control mode can operate.

Select or deselect these checkboxes to display the related controls on
the Adjustments tab.

Show F Gain

Show F2 Gain

Show S Gain

Show S2 Gain

Show PF Gain

Auto-Tuning Control Panel

This control panel automatically calculates tuning values for PIDF control modes.

Access

Panel Buttons >

Auto-Tuning Control Panel

Description

Item

Selects the control channel to auto-tune.

Control Channel

Selects the control mode to be in when auto-tuning. This mode setting
can be different than the “Mode to Tune” setting.

Control Mode

Selects the mode that is to be tuned.

Mode to Tune

Displays the active control mode.

Active Mode

Selects an auto-tuning type.

Auto-Tuning Type

Basic—When you run Basic auto-tuning, the auto-tuner disregards your
current PIDF gain settings and exercises the actuator to within 80% of
the Upper Limit and the Lower Limit.

Advanced—When you run Advanced auto-tuning, the auto-tuner first
does basic auto-tuning. It then runs a sine sweep to exercise the actuator

240 MTS Series 793 Control Software

Station Setup