MTS Series 793 User Manual

Page 284

Advertising
background image

Detector Action Settings

Action

Setting

No action occurs. This setting dims the indicator.

Disabled

Writes a message to the Message Log and the indicator switches from white
to red.

Indicate

Stops any program command, writes a message to the Message Log, turns
off pressure at the hydraulic service manifold (HSM), and switches the indicator
from green to red.

Station Power Off

For single station systems: If the “Last Off” function is enabled in the .hwi file
or equivalent jumpering, the hydraulic power unit (HPU) is turned off. If the
“Last Off” function is disabled, the HPU will remain on.

For multistation systems: If the “Last Off” function is enabled in the .hwi file or
equivalent jumpering, the hydraulic power unit (HPU) will be turned off only if
the interlock occurs on the last station running. If the “Last Off” function is
disabled, the HPU will remain on.

Stops any program command, writes a message to the Message Log, clamps
the servovalve (if enabled in the .hwi file), turns off pressure at the hydraulic
service manifold (HSM), and switches the indicator from green to red.

Interlock

Note:

An Interlock must be reset to resume testing.

For single station systems: If the “Last Off” function is enabled in the .hwi file
or equivalent jumpering, the hydraulic power unit (HPU) is turned off. If the
“Last Off” function is disabled, the HPU will remain on.

For multistation systems: If the “Last Off” function is enabled in the .hwi file or
equivalent jumpering, the hydraulic power unit (HPU) will be turned off only if
the interlock occurs on the last station running. If the “Last Off” function is
disabled, the HPU will remain on.

284 MTS Series 793 Control Software

Station Setup

Advertising