Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 101
Programming
5-33
Feature Select Group
(continued)
[Reset/Run Time]
Parameter # 15
Factory Default 1.0 Sec
[Reset/Run Time]
Parameter Type Read & Write
Minimum 0.5 Sec
This value sets the time between restart attempts when
[Reset/Run Tries] is a value other than zero.
Important: [Reset/Run Tries] is a cumulative count. This
counter resets to zero if four (4) minutes elapses since the
last fault.
Units 0.1 Second
Maximum 30.0 Sec
[S Curve Enable]
Parameter # 57
Factory Default ‘‘Disabled”
[S Curve Enable]
Parameter Type Read & Write
This parameter enables a fixed shape S-Curve.
Units Text
Settings ‘‘Enabled”
‘‘Disabled”
a
a
Decel Time
1 or 2
Accel Time
1 or 2
'
a
'
Enabled
Disabled
Figure 5.16 S-Curve
Accel/Decel times are double the active accel/decel time
settings.
Important: The setting for [S-Curve Time] must be 0.
Important: If [Stop Select] is set to “S Curve” then the decel
time will be double the active decel setting when a stop
command is provided.
2X Accel Time 1 or 2
'
'
2X Decel Time 1 or 2
a