Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 101

Advertising
background image

Programming

5-33

Feature Select Group

(continued)

[Reset/Run Time]

Parameter # 15

Factory Default 1.0 Sec

[Reset/Run Time]

Parameter Type Read & Write

Minimum 0.5 Sec

This value sets the time between restart attempts when
[Reset/Run Tries] is a value other than zero.

Important: [Reset/Run Tries] is a cumulative count. This
counter resets to zero if four (4) minutes elapses since the
last fault.

Units 0.1 Second

Maximum 30.0 Sec

[S Curve Enable]

Parameter # 57

Factory Default ‘‘Disabled”

[S Curve Enable]

Parameter Type Read & Write

This parameter enables a fixed shape S-Curve.

Units Text

Settings ‘‘Enabled”

‘‘Disabled”

a

a

Decel Time

1 or 2

Accel Time

1 or 2

'

a

'

Enabled

Disabled

Figure 5.16 S-Curve

Accel/Decel times are double the active accel/decel time
settings.

Important: The setting for [S-Curve Time] must be 0.

Important: If [Stop Select] is set to “S Curve” then the decel
time will be double the active decel setting when a stop
command is provided.

2X Accel Time 1 or 2

'

'

2X Decel Time 1 or 2