Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 99

Advertising
background image

Programming

5-31

Frequency Set Group

(continued)

Table 5.C Motor Operated Potentiometer (MOP) Frequency Source and Accel/Decel Selection

Parameter Settings

Frequency Source

Accel/Decel

Control Terminal Block

Preset/

2nd Accel (26)

Upper Presets

(72)

Freq

Select 1

(5)

Freq

Select 2

(6)

Accel

Time 1

(7)

Decel

Time 1

(8)

Accel

Time 2

(30)

Decel

Time 2

(31)

SW3

TB2-18

SW2

TB2-17

SW1

TB2-16

Preset

or

Disabled

or

0

MOP Decrement

➁ MOP Increment ➂

or

2nd Accel

or

Enabled

X

MOP Decrement

➁ MOP Increment ➂

The parameter [Freq Source] indicates the active frequency source. See p. 5-45.
MOP Decrement – When this switch is closed, [MOP Hz] is decreased at the rate programmed in [MOP Increment].
MOP Increment – When this switch is closed, [MOP Hz] is increased at the rate programmed in [MOP Increment].

Indicates active function/parameter.

X

Indicates closed switch.

0

Indicates open switch.

(26) Indicates parameter number.

[Analog Filter]

Parameter # 144

Factory Default 100%

[Analog Filter]

Parameter Type Read & Write

Selects the amount of software filtering applied to the
0-10 volt analog input and potentiometer input in 25%
increments. The lower the percentage, the less filtering
applied – allowing faster response to analog signal
changes. To obtain higher noise immunity, set the filter
value higher.

A value of 100% represents the same amount of filtering as
all previous versions of released firmware. With this setting
the frequency command rises to 95% of the signal input in
0.5 seconds.

Units Text

Settings “0%”

“25%”
“50%”
“75%”
“100%”