Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 147

Advertising
background image

Serial Communications

B-5

Table B.4 Parameter Grouping/User Settings

Group Parameter Name

Parameter
Number

Display
Units

Drive Units
Scale Factor

Minimum

Maximum

Factory Setting

User‘s
Setting

Output Current

54

Amps

100

0.00

Two times drive output current

––

Output Voltage

1

Volts

100

0

Maximum Voltage

––

Output Power

23

kW

100

0.00

Two times rated drive output power

––

ering

DC Bus Voltage

53

Volts

1

0

410 - 230V Drive
815 - 460V Drive

––

M

et

e

Output Freq

66

Hz

32767 = Max. Freq

Max. Frequency

Maximum Frequency

––

M

Freq Command

65

Hz

100

0.00

+400.00

0.00

MOP Hz

42

Hz

100

0.00

400.00

––

Drive Temp

70

Degrees C

1

0

100

––

Last Fault

4

Numeric

1

0

Max. Fault Number

––

% Output Power

3

%

1

0

200% Drive Rated Power

––

% Output Curr

2

%

1

0

200% of Rated Drive Output Current

––

Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions

Refer to page B-2.