Programming

5-40

Faults Group

(continued)

[Cur Lim Trip En]

Parameter # 82

Factory Default ‘‘Default Run”

[Cur Lim Trip En]

Parameter Type Read & Write

This setting determines whether or not exceeding the
setting in [Current Limit] will cause a Diagnostic Current

Units Text

Setting ‘‘Trip @ I Lim”

A Diagnostic Current Limit Fault is generated

setting in [Current Limit] will cause a Diagnostic Current
Limit Fault (Fault F36).

‘‘Default Run”

No fault generated

[Line Loss Fault]

Parameter # 40

Factory Default ‘‘F03 Enable”

[Line Loss Fault]

Parameter Type Read & Write

This setting determines whether a 15% drop in DC Bus
voltage will have no effect on operation or cause a ‘‘Power
Loss Fault” (fault F03).

Units Text

Setting ‘‘UVolt Run”

‘‘Power Loss Fault” Disabled

Loss Fault (fault F03).

Important

:

The “Line Loss” alarm bit will be set when this

condition exists regardless of the parameter setting.

‘‘FO3 Enable”

Drive Trips at 85% of nominal bus voltage.