Programming

5-35

Feature Select Group

(continued)

[Cable Length]

Parameter # 143

Factory Default “Short”

[Cable Length]

Parameter Type Read & Write

This parameter selects the length of cable that is
connected to the motor.

Important: A setting of “Long” causes the PWM carrier
frequency to be fixed at 2 kHz and Voltage Ring-Up
Reduction software to be enabled.

Important: If “Overload Fault” (F7) occurs – choose “Long”
length.

Units Text

Settings “Short”

“Long”

[Rated Slip]

Parameter # 146

Factory Default 2.0 Hz

[Rated Slip]

Parameter Type Read & Write

Minimum 0.0 Hz

This parameter compensates for the inherent slip in an
i d ti

t

A f

i

dd d t th

d d

Units 0.1 Hz

Maximum 5.0 Hz

p

p

p

induction motor. A frequency is added to the commanded
output frequency based on torque current. The actual value
added may be viewed in [Slip Comp Adder] (parameter
148). If motor shaft speed decreases significantly under
heavy loads then this value should be increased. A setting
of 0.0 Hz disables the function.

This parameter can be set more accurately based on motor
nameplate RPM at full load. Use the formula and table
shown.

Motor Sync Speed – Nameplate RPM

Motor Sync Speed

Motor

Nameplate

Hertz

Drive Rated Amps

Motor FLA

x

x

Rated Slip =

Example
Drive 1 HP, 460V

2.3 Amps Rated

Motor Motor Sync Speed = 1800 RPM

Nameplate RPM = 1725 RPM
Nameplate Hertz = 60 Hz
Motor FLA = 1.7 Amps

[(

)]

1800 – 1725

1800

60

2.3

1.7

x

x

Rated Slip =

[(

)]

) ( ) (

= 3.38 Hz

Note: Instability may occur if [Rated Slip] is set too high with operating frequencies below 10 Hz.

Motor Sync Speed
Poles

60 Hz

50 Hz

2

3600

3000

4

1800

1500

6

1200

1000

8

900

750

12

600

500

(

)

)

(

Set [Rated Slip] to 3.4 Hz.