Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 116

Advertising
background image

Programming

5-48

Masks Group

(continued)

[Start Mask]

Parameter # 95

Factory Default 01111111

[Start Mask]

Parameter Type Read & Write

This parameter determines which adapters can issue start
commands.

Units Byte

Settings 1

0

Permit Control
Deny Control

[Jog Mask]

Parameter # 96

Factory Default 01111111

[Jog Mask]

Parameter Type Read & Write

This parameter determines which adapters can issue jog
commands.

Units Byte

Settings 1

0

Permit Control
Deny Control

[Reference Mask]

Parameter # 97

Factory Default 01111111

[Reference Mask]

Parameter Type Read & Write

This parameter determines which adapters can control the
switching between the available freq. reference sources.
Important: Terminal Block (TB2) will have control unless
masked out.

Units Byte

Settings 1

0

Permit Control
Deny Control

[Accel Mask]

Parameter # 98

Factory Default 01111111

[Accel Mask]

Parameter Type Read & Write

This parameter determines which adapters can switch
between [Accel Time 1] and [Accel Time 2].
Important: Terminal Block (TB2) will have control unless
masked out.

Units Byte

Settings 1

0

Permit Control
Deny Control

[Decel Mask]

Parameter # 99

Factory Default 01111111

[Decel Mask]

Parameter Type Read & Write

This parameter determines which adapters can switch
between [Decel Time 1] and [Decel Time 2].
Important: Terminal Block (TB2) will have control unless
masked out.

Units Byte

Settings 1

0

Permit Control
Deny Control

Advertising