Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 89

Advertising
background image

Programming

5-21

Advanced Setup Group

(continued)

[Analog Invert]

Parameter # 84

Factory Default ‘‘Disabled”

[Analog Invert]

Parameter Type Read & Write

This parameter enables the inverting function for the 0-10
Volt and 4-20mA analog input signal at TB2.

Units Text

Settings ‘‘Enabled”

Maximum Input Commands [Minimum Freq]
Minimum Input Commands [Maximum Freq]

Volt and 4-20mA analog input signal at TB2.

‘‘Disabled”

Maximum Input Commands [Maximum Freq]
Minimum Input Commands [Minimum Freq]

Figure 5.12 Analog Invert

[Maximum Frequency]

'

0 V
4 mA

Drive Output

y

10 V
20 mA

y

[Minimum Frequency]

'

Disabled

Enabled

[4-20mA Loss Sel]

Parameter # 81

Factory Default ‘‘Stop/Fault”

[4 20mA Loss Sel]

Parameter Type Read & Write

This parameter selects the drives reaction to a loss of a
4 20 A i

l h

th

ti

[F

S

] i

Units Text

Settings ‘‘Stop/Fault”

Drive Stops and Issues ‘‘Hz Err Fault” (F29)

p

4-20mA signal when the active [Frequency Source] is
4 20mA Important: The drive output contacts can be

‘‘Hold/Alarm”

Drive Maintains Last Output Freq and sets an Alarm bit

4-20mA. Important: The drive output contacts can be
used to issue an alarm signal by setting [Output 1 Config]

‘‘Max/Alarm”

Drive Outputs [Maximum Freq] and sets Alarm bit

used to issue an alarm signal by setting [Output 1 Config]
or [Output 2 Config] to “alarm”. Important: Loss of signal

‘‘Pre1/Alarm”

Drive Outputs [Preset Freq 1] and sets an Alarm bit

or [Output 2 Config] to alarm . Important: Loss of signal
is defined as a signal < 3.5 mA or a signal > 20.5 mA.

‘‘Min/Alarm”

Drive Outputs [Minimum Freq] and sets an Alarm bit