Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 149

Advertising
background image

Serial Communications

B-7

Table B.4 Parameter Grouping/User Settings

(continued)

Group Parameter Name

Parameter
Number

Display
Units

Drive Units
Scale Factor

Minimum

Maximum

Factory Setting

User‘s
Setting

Minimum Freq

16

Hz

1

0

120

0

Maximum Freq

19

Hz

1

40

400

60

Base Frequency

17

Hz

1

40

400

60

Base Voltage

18

Volts

1

25% of DRV

100% of Max. Drive Rated Volts

Maximum DRV

Break Frequency

49

Hz

1

0

120

30

p

Break Voltage

50

Volts

1

0

50% of Max Drive Rated Volts

Drive Size
Dependent

t Up

Maximum Voltage

20

Volts

1

25% of DRV

110% of Max. Drive Rated Volts

Maximum DRV

Set

DC Boost Select

9

Text

1

––

––

Break Point

anced

S

Start Boost

48

Volts

1

0

25% of Max. Drive Rated Volts

Drive Size
Dependent

d

va

n

Run Boost

83

Volts

1

0

25% of Max. Drive Rated Volt

0

Ad

v

PWM Frequency

45

kHz

10

2.0

8.0

4.0

Analog Invert

84

Text

1

––

––

Disabled

4–20 mA Loss Sel

81

Text

1

––

––

Stop/Fault

Stop Select

10

Text

1

––

––

Ramp

DC Hold Time

12

Seconds

100

0.0

150.0

0.0

DC HoId Volts

13

Volts

1

0

25% of Max. Drive Rated Volts

0

DB Enable

11

Text

1

––

––

Disabled

Motor Type

41

Text

1

––

––

Induc/Reluc

Compensation

52

Text

1

––

––

Comp

Refer to Table B.1 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions.

Refer to page B-2.

Advertising