Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 94

Advertising
background image

Programming

5-26

Frequency Set Group

(continued)

[Jog Frequency]

Parameter # 24

Factory Default 10.0 Hz

[Jog Frequency]

Parameter Type Read & Write

Minimum 0.0 Hz

This parameter sets the frequency the drive will output
when it receives a jog command.

Units 0.1 Hz

Maximum 400.0 Hz

[Prst/2nd Accel]

Parameter # 26

Factory Default “Preset”

[Prst/2nd Accel]

Parameter Type Read & Write

This parameter, along with the [Upper Presets] parameter,
determines which frequency source and Accel/Decel
parameters will be selected using the optional inputs SW1,
SW2 and SW3. Refer to charts on Pages 5-29 and 5-30.

Units Text

Settings “Preset”

“2nd Accel”

[Upper Presets]

Parameter # 72

Factory Default “Disabled”

[Upper Presets]

Parameter Type Read & Write

This parameter along with the [Prst/2nd Accel] parameter
determines which frequency source and Accel/Decel
parameters will be selected using the optional inputs SW1,
SW2 and SW3. Refer to charts on Pages 5-29 and 5-30.

Units Text

Settings “Enabled”

“Disabled”

[Accel Time 2]

Parameter # 30

Factory Default 5.0 Sec

[Accel Time 2]

Parameter Type Read & Write

Minimum 0.0 Sec

This value determines the time it will take the drive to ramp
from 0 Hz to [Maximum Frequency]. The rate is linear
unless [S Curve] is ‘‘Enabled.” It applies to any increase
in command frequency unless [Accel Time 1] is selected.
Refer to charts on Pages 5-29 and 5-30.

Units 0.1 Second

Maximum 3600.0 Sec